Products Search Repair Government Tech Support Contact Us
| ||||||||
AVO Megger 550005B
|
Megger 550005B Discounted Pricing 619-474-4477 619-474-4477 $4,295.00 |
Megger (550005B) Single Phase TTR Transformer Turns Ratio Test Set
Download Datasheet via Adobe PDF file
| ||
|
The Megger Single Phase 550005 TTR, Transformer Turns Ratio Test Set, measures the turns ratio and exciting current of windings in power, potential and current transformers. Deviations in turns ratio readings indicate problems in one or both windings or the magnetic core circuit. The Megger 550005 TTR test set aids in identifying: · Shorted coils · Open circuits · Incorrect connections · Internal faults or tap-changer defects in step regulators as well as in transformers. The Biddle Megger 550005 single phase model is available in either hand-cranked or line-operated versions and measures highly sensitive turns ratios of up to 129.99:1 with accuracy of ±0.1%. An optional auxilary transformer extends the ratio range to 329.99:1. The AVO Megger 550005 TTR set operates on the principle that the voltage ratio of the transformer at no load is practically equal to the true turns ratio. The major source of error in a transformer is a primary impedance drop due to magnetizing current, which is kept to a minimum by excitation at a fraction of rated voltage. By employing a design that meets both of these conditions along with the use of a null balance system, the turns ratio of a transformer can be determined accurately. When measuring the turns ratio of distribution and power transformers, the accuracy is well within 0.1%.
| |||